DSZH R410 leak connector - 5 gr/year
DSZH R410 leak connector is a reference leak element for HVAC system testing, delivering a controlled leak rate of 5 g/year with ±25% tolerance. Features SAE 1/4" flared connection, 316L stainless steel body, and…
SKU 3G-CBM-01465
Local availability & support — Singapore
- Local office
- 20 Woodlands Link #09-05, Singapore 738733
- Phone
- +65 8878 8355
- Delivery
- Same-day or next-business-day delivery within Singapore for in-stock items; 7–14 days for factory-order parts from Europe.
- Payment
- Invoicing in SGD. PayNow, bank transfer, and corporate PO accepted.
- Ships to
- Singapore
Need installation or engineering help?
Ask a question
Product Description
DSZH R410 leak connector is a reference leak element for HVAC system testing, delivering a controlled leak rate of 5 g/year with ±25% tolerance. Features SAE 1/4" flared connection, 316L stainless steel body, and Viton O-ring seal for FGas-compliant applications.
Frequently Asked Questions
What is the DSZH R410 leak connector used for?
The DSZH R410 leak connector is a reference leak element used by HVAC engineers to verify refrigerant leak detector sensitivity. It delivers a controlled 5 g/year leak rate for FGas compliance testing, helping technicians confirm their equipment meets EN-14624 standards during service or quality control operations.
What are the specifications of the DSZH R410 leak connector?
The DSZH R410 leak connector has a leak rate of 5 g/year with ±25% tolerance, SAE 1/4" flared connection with 7/16 UNF thread, 316L stainless steel body, Viton O-ring seal (4mm x 3mm), and weighs 50 grammes. It includes an FGas compliance certificate and is designed and manufactured in the UK.
Where to buy the DSZH R410 leak connector in Singapore?
You can source the DSZH R410 leak connector through 3G Electric in Singapore. We provide procurement, logistics, customs clearance, and delivery services for this HVAC tool. Contact us for pricing and lead time on orders.
How to use the DSZH R410 leak connector for detector testing?
Install the DSZH R410 leak connector at the outlet of a refrigerant supply to produce a 5 g/year flow. Place your leak detector probe at the connector's outlet; if the detector responds, it is sensitive enough for FGas compliance per EN-14624. Regularly test to identify battery or sensor issues affecting performance.
Used in
Common applications for DSZHDSZH Products
3G Electric supplies DSZH hvac tools. We supply genuine products with in-stock availability on common SKUs, technical documentation, commissioning support, and warranty service — worldwide.