Danfoss Transformer type ZT930
Danfoss ZT930 ignition transformer for oil burner and combustion applications delivers 2 x 7 kV ignition voltage from 220/240 V supply at 50 Hz. Features ferrite core design with 33% duty cycle in 3 minutes and…
SKU 3G-CBM-06960
Also listed as: TRF 05152 · TRF-05152
Local availability & support — Singapore
- Local office
- 20 Woodlands Link #09-05, Singapore 738733
- Phone
- +65 8878 8355
- Delivery
- Same-day or next-business-day delivery within Singapore for in-stock items; 7–14 days for factory-order parts from Europe.
- Payment
- Invoicing in SGD. PayNow, bank transfer, and corporate PO accepted.
- Ships to
- Singapore
Need installation or engineering help?
Ask a question
Product Description
Danfoss ZT930 ignition transformer for oil burner and combustion applications delivers 2 x 7 kV ignition voltage from 220/240 V supply at 50 Hz. Features ferrite core design with 33% duty cycle in 3 minutes and secondary current of 40 mA rms, suitable for industrial heating systems.
Frequently Asked Questions
What is the Danfoss ZT930 ignition transformer used for?
The Danfoss ZT930 ignition transformer is used for oil, gas, and combination burners in industrial heating systems. It generates a high-frequency spark for reliable ignition, even in high-output air fans, and is suitable for mounting under automatic control box bases.
What are the specifications of the Danfoss ZT930 ignition transformer?
The Danfoss ZT930 operates on 220/240 V supply at 50 Hz (40-60 Hz) with a supply tolerance of -15% to +10%. It delivers 2 x 7 kV ignition voltage, has a secondary current of 40 mA rms, a 33% duty cycle in 3 minutes, and a ferrite core design with 20 kHz oscillator frequency.
Where to buy the Danfoss ZT930 ignition transformer in Singapore?
You can source the Danfoss ZT930 ignition transformer through 3G Electric in Singapore. We handle logistics, customs clearance, and delivery to your facility. Contact us for availability and lead time on this item.
How to install the Danfoss ZT930 ignition transformer?
Mount the Danfoss ZT930 under the control box base using the provided fixing holes. Connect the primary supply via three-pole Fast-in/Fast-on AMP connectors. High-tension connections accept either Ø 1 mm or Ø 4 mm pins. Ensure ambient temperature stays between -10°C and +60°C.