The Fireye SureFire II High Tension Spark & Sense Igniter (Model HTSS) is a spark igniter designed for industrial burner systems. It carries CE and FM Approvals for safety and compliance.
SKU 3G-OTH-02834
Also listed as: SUREFIREIIHIGHTENSIONSENSE · SUREFIRE II HIGH TENSION SENSE
Local availability & support — Singapore
- Local office
- 20 Woodlands Link #09-05, Singapore 738733
- Phone
- +65 8878 8355
- Delivery
- Same-day or next-business-day delivery within Singapore for in-stock items; 7–14 days for factory-order parts from Europe.
- Payment
- Invoicing in SGD. PayNow, bank transfer, and corporate PO accepted.
- Ships to
- Singapore
Need installation or engineering help?
Ask a question
Product Description
The Fireye SureFire II High Tension Spark & Sense Igniter (Model HTSS) is a spark igniter designed for industrial burner systems. It carries CE and FM Approvals for safety and compliance.
Frequently Asked Questions
What is the Fireye SureFire II High Tension Spark & Sense Igniter used for?
The Fireye SureFire II HTSS igniter is used to ignite gaseous fuels such as natural gas, propane, or LPG in natural and forced draught gas igniters, pilots, and small capacity gas burners. Its Spark & Sense feature also provides flame detection via ionization current sensing after ignition.
What are the specifications of the Fireye SureFire II HTSS igniter?
The Fireye SureFire II HTSS operates on 230/110 VAC, 50/60 Hz, with an ignition transformer output of 8,000 VAC at 15 mA. It uses a 24 VDC ignition control signal, has a rod insertion length of 0.65 to 3.15 m, and a 16 mm diameter 316 SS rod. It is CE and FM Approved.
Where to buy the Fireye SureFire II HTSS igniter in Singapore?
You can source the Fireye SureFire II HTSS igniter through 3G Electric in Singapore. We handle logistics, customs clearance, and delivery to your facility. Contact us for pricing and lead time on this industrial ignition component.
How does the Spark & Sense feature work on the Fireye SureFire II igniter?
The Spark & Sense feature uses ionization current sensing to detect flame presence. After the igniter sparks to ignite the fuel-air mixture, the same rod measures the electrical conductivity of the ionized gas in the flame, providing flame safeguard functionality without a separate sensor.