From the manufacturer's datasheet
PactrolSupply voltage
220 V +10% -15%, single phase
Frequency
50 Hz
Motor rating
220 V, 4 A
Ignition transformer rating
220 V, 2 A
Signaling rating
220 V, 2 A
Minimum cell illumination
15 Lux
Max ambient temperature (equipment)
50 °C
Max ambient temperature (cell)
70 °C
Features
- Pre-ventilation time approx. 15 sec.
- Pre-ignition time approx. 15 sec.
- Delay between first and second stage approx. 30 sec.
- Post-ignition time 2 sec.
- Safety time 10 sec.
- Power consumption in normal operation 6 VA
Typical applications
For two-stage burnersUsed with flame cell types 8208 or 8209
Use only in single-phase 220 V supply with +10% -15% tolerance.
Ensure minimum cell illumination of 15 Lux.
Select a size
Showing 14 / 14 variants — scroll the table for more
| Part No (MPN)— | 3G SKU3G-CBM-05933 | Model310 | |
| Part No (MPN)— | 3G SKU3G-CBM-05934 | Model610 | |
| Part No (MPN)— | 3G SKU3G-CBM-05935 | Model803 | |
| Part No (MPN)— | 3G SKU3G-CBM-05936 | Model810 | |
| Part No (MPN)— | 3G SKU3G-CBM-05937 | Model23 | |
| Part No (MPN)— | 3G SKU3G-CBM-05938 | Model26 | |
| Part No (MPN)— | 3G SKU3G-CBM-05939 | Model28 | |
| Part No (MPN)— | 3G SKU3G-CBM-05940 | Model29 | |
| Part No (MPN)— | 3G SKU3G-CBM-05941 | Model41 | |
| Part No (MPN)— | 3G SKU3G-CBM-05942 | Model43 | |
| Part No (MPN)— | 3G SKU3G-CBM-05943 | Model45 | |
| Part No (MPN)— | 3G SKU3G-CBM-05944 | Model52 | |
| Part No (MPN)— | 3G SKU3G-CBM-05945 | Model55 | |
| Part No (MPN)— | 3G SKU3G-CBM-05948 | Model72 |
Not sure this is the right part? Get a recommendation.
Need installation or engineering help?
Installation, commissioning, maintenance plans, system design, and bundled product + service quotes — one team handles the full scope.
Talk to an engineerAsk a question
Frequently Asked Questions
What is the safety time?
The safety time is 10 seconds.
What is the delay between first and second stage?
The delay is approximately 30 seconds.
What is the maximum ambient temperature for the cell?
The maximum ambient temperature for the cell is 70 °C.