Honeywell Relay MMI 810.33
Honeywell Relay MMI 810.33 is a burner control relay rated for 220/240 V supply with IP 44 protection and operating range of -20°C to +60°C. Designed for industrial heating and combustion applications requiring…
SKU 3G-CBM-05905
Local availability & support — Singapore
- Local office
- 20 Woodlands Link #09-05, Singapore 738733
- Phone
- +65 8878 8355
- Delivery
- Same-day or next-business-day delivery within Singapore for in-stock items; 7–14 days for factory-order parts from Europe.
- Payment
- Invoicing in SGD. PayNow, bank transfer, and corporate PO accepted.
- Ships to
- Singapore
Need installation or engineering help?
Ask a question
Product Description
Honeywell Relay MMI 810.33 is a burner control relay rated for 220/240 V supply with IP 44 protection and operating range of -20°C to +60°C. Designed for industrial heating and combustion applications requiring reliable control at 50-60 Hz frequencies.
Frequently Asked Questions
What is the Honeywell Relay MMI 810.33 used for?
The Honeywell Relay MMI 810.33 is a burner control relay used in industrial heating and combustion systems. It controls and monitors forced-draft gas and dual-fuel burners, including those on hot-air generators, ensuring safe automatic operation and flame supervision per EN 298.
What are the specifications of the Honeywell MMI 810.33?
The Honeywell MMI 810.33 operates on 220/240 V supply at 50-60 Hz, with IP 44 protection and an ambient temperature range of -20°C to +60°C. It has a classification of BTLLXN per EN 298, a maximum load of 10 A fast or 6 A time-delay, and supports ionization or infrared flame detection.
Where to buy the Honeywell MMI 810.33 in Singapore?
You can source the Honeywell MMI 810.33 from 3G Electric in Singapore. We handle logistics, customs clearance, and delivery to your facility. Contact us for pricing and lead time on this burner control relay.
How to install the Honeywell MMI 810.33 burner control?
Mount the Honeywell MMI 810.33 in any position within a clean, dry enclosure. Connect the supply voltage (220/240 V, 50-60 Hz) and flame detector (ionization probe or IRD 1020) using cable runs up to 20 m. Ensure the ambient temperature stays between -20°C and +60°C and that the protection class IP 44 is maintained.
Used in
Common applications for HoneywellHoneywell Products
3G Electric supplies Honeywell burner controls. We supply genuine products with in-stock availability on common SKUs, technical documentation, commissioning support, and warranty service — worldwide.