Combutech UV1p detection cell
Combutech UV1p detection cell is a combustion flame detector with spectral response of 185–260 nm, housed in Ø 35 × 80 mm body rated IP65. Recovery time of 20 µS at 10% duty cycle ensures fast flame signal…
SKU 3G-CBM-01173
Also listed as: COB 02082 · COB-02082
Local availability & support — Singapore
- Local office
- 20 Woodlands Link #09-05, Singapore 738733
- Phone
- +65 8878 8355
- Delivery
- Same-day or next-business-day delivery within Singapore for in-stock items; 7–14 days for factory-order parts from Europe.
- Payment
- Invoicing in SGD. PayNow, bank transfer, and corporate PO accepted.
- Ships to
- Singapore
Need installation or engineering help?
Ask a question
Product Description
Combutech UV1p detection cell is a combustion flame detector with spectral response of 185–260 nm, housed in Ø 35 × 80 mm body rated IP65. Recovery time of 20 µS at 10% duty cycle ensures fast flame signal processing. Suitable for industrial burner control and safety systems requiring ultraviolet flame monitoring.
Frequently Asked Questions
What is the Combutech UV1p detection cell used for?
The Combutech UV1p detection cell is a compact ultraviolet flame detector used in industrial burner control and safety systems. It monitors gas, oil, or dual-fuel burner flames by sensing UV radiation in the 185–260 nm spectral range, providing fast flame signal processing for reliable safety shut-off.
What are the specifications of the Combutech UV1p detection cell?
The Combutech UV1p has a spectral response of 185–260 nm, supply voltage 230 VAC ±15%, recovery time 20 µS at 10% duty cycle, and maximum discharge current 30 mA. It is housed in a Ø 35 x 80 mm IP65-rated body with a 3-pole DIN43650A/ISO4400 connection and operates from -20 to 90 °C.
Where to buy the Combutech UV1p detection cell in Singapore?
You can source the Combutech UV1p detection cell through 3G Electric in Singapore. We handle logistics, customs clearance, and delivery to your facility. Contact us for pricing and lead time on this combustion flame detector.
How to install the Combutech UV1p detection cell?
Mount the Combutech UV1p in any position, but avoid vertical mounting where combustion products can fill the volume in front of the phototube. If the peepsight temperature exceeds 70 °C, apply cooling air to the optional ¼" GAS connection. Wire per the 3-pole DIN43650A/ISO4400 connector; phase/neutral reversal will not damage the detector but will prevent a useful flame signal.
Used in
Common applications for CombutechCombutech Products
3G Electric supplies Combutech combustion. We supply genuine products with in-stock availability on common SKUs, technical documentation, commissioning support, and warranty service — worldwide.