TG Safety aquastat internal adjustment manual reset 90-110°C capillary 3m
TG safety aquastat with internal manual reset for hydronic heating systems, featuring 90-110°C adjustment range and 3 m capillary length. M10x1 connection for boiler thermal protection applications.
SKU 3G-CBM-06931
Also listed as: THG 70004 · THG-70004
Local availability & support — Singapore
- Local office
- 20 Woodlands Link #09-05, Singapore 738733
- Phone
- +65 8878 8355
- Delivery
- Same-day or next-business-day delivery within Singapore for in-stock items; 7–14 days for factory-order parts from Europe.
- Payment
- Invoicing in SGD. PayNow, bank transfer, and corporate PO accepted.
- Ships to
- Singapore
Need installation or engineering help?
Ask a question
Product Description
TG safety aquastat with internal manual reset for hydronic heating systems, featuring 90-110°C adjustment range and 3 m capillary length. M10x1 connection for boiler thermal protection applications.
Frequently Asked Questions
What is a TG safety aquastat with manual reset used for?
A TG safety aquastat with internal manual reset is used for boiler thermal protection in hydronic heating systems. It limits temperature by cutting off the burner if the water exceeds the set point, requiring manual reset after a trip. This prevents overheating and ensures safe operation in residential and commercial boilers.
What are the specifications of the TG safety aquastat 3G-CBM-06931?
The TG safety aquastat 3G-CBM-06931 has a temperature range of 90-110°C, a tolerance of +0 -6°C, and a manual reset differential of 20-45°C. It features a 3 m copper capillary with PVC protection, M10x1 connection, and contact rating of 16(4)A 250V~. The sensing element withstands up to 135°C, and insulation grade is II.
Where to buy a TG safety aquastat in Singapore?
You can source the TG safety aquastat 3G-CBM-06931 from 3G Electric in Singapore. We supply this TG thermostat for hydronic heating applications, handling logistics, customs clearance, and delivery to your facility. Contact us for pricing and lead time on this manual reset safety aquastat.
How to install a TG safety aquastat with manual reset?
Install the TG safety aquastat by screwing the M10x1 connection into the boiler thermal well. Use heat-resistant conductors rated at least T 130°C. The unit must be earthed via the tab terminal. After installation, set the temperature between 90-110°C. If the aquastat trips, press the internal manual reset button after the system cools.
Used in
Common applications for TGTG Products
3G Electric supplies TG thermostats. We supply genuine products with in-stock availability on common SKUs, technical documentation, commissioning support, and warranty service — worldwide.