OEM Self-regulating heating cable K55A100 (100m coil)
The OEM K55A100 is a self-regulating heating cable supplied as a 100 m coil, with a nickel-plated copper conductor of 1.25 mm² cross-section, polyolefin insulation, and a braided copper sheath with modified…
SKU 3G-CBM-03628
Local availability & support — Singapore
- Local office
- 20 Woodlands Link #09-05, Singapore 738733
- Phone
- +65 8878 8355
- Payment
- Invoicing in SGD. PayNow, bank transfer, and corporate PO accepted.
Need installation or engineering help?
Ask a question
Product Description
The OEM K55A100 is a self-regulating heating cable supplied as a 100 m coil, with a nickel-plated copper conductor of 1.25 mm² cross-section, polyolefin insulation, and a braided copper sheath with modified polyolefin outer. It delivers 9 W/m and is designed to maintain the temperature of fluids in pipes, including domestic hot water, at temperatures above 70°C to avoid Legionellosis bacteria; heat emission varies automatically without control thermostats, and a thermostat (L03BI1A) can be used for periodic heating or constant temperature. The cable has a minimum bending radius of 27 mm, a maximum heating-circuit length of 130 m, and can be cut to length during installation.
Frequently Asked Questions
What is the OEM K55A100 self-regulating heating cable used for?
The OEM K55A100 is a self-adjusting heating cable for freeze protection and temperature maintenance in industrial piping systems. Per the manufacturer datasheet, it is suitable for maintaining the temperature of liquids in pipes, such as domestic hot water, and can hold pipes above 70 °C to help avoid the formation of Legionellosis bacteria.
What are the specifications of the OEM K55A100 heating cable?
The OEM K55A100 is supplied as a 100 m coil with nickel-plated copper conductors of 1.25 mm² cross-section, polyolefin insulation, and a braided copper sheath with modified polyolefin outer. Minimum bending radius is 27 mm. Per the datasheet it delivers 9 W/m at 55 °C, runs on 230 V 50 Hz, and permits a maximum heating circuit length of 130 m.
How should the OEM K55A100 heating cable be installed?
Per the manufacturer datasheet, secure the cable linearly to the pipe with K50 fixing tape for steel pipes or K50AL for plastic pipes, and apply an insulating coating over the cable for an effective system. The cable can be cut to length on site, minimum bending radius is 27 mm, and a cold tail end must be created using the KIT2A kit. A thermostat such as the L03BI1A can be used to maintain a constant system temperature.
Where to buy the OEM K55A100 self-regulating heating cable worldwide?
3G Electric supplies the OEM K55A100 100 m coil worldwide, handling logistics, customs, and delivery to your site. Contact us with your pipe diameter, circuit length, and voltage requirements for a quote and lead time. The product carries CSTB homologation per the manufacturer datasheet.